斜拉桥主梁钢-UHPC组合桥面板抗压稳定性能试验研究

EXPERIMENTAL STUDY ON COMPRESSIVE STABILITY OF STEEL–UHPC COMPOSITE DECKS FOR MAIN GIRDERS OF CABLE-STAYED BRIDGES

  • 摘要: 为明确大跨斜拉桥轻型组合主梁中钢-超高性能混凝土(ultra-high performance concrete,UHPC)组合桥面板的抗压稳定性能,以钢面板厚度、UHPC层厚度以及加劲肋形状等为试验参数,设计制作了5个1∶2几何缩尺比全钢和钢-UHPC组合桥面板试件并分别对其轴压稳定性能进行了试验研究。结果表明:全钢试件均呈现分支点失稳模态,组合试件由于UHPC层的加强作用及钢板件局部屈曲后截面上钢与UHPC层间存在的应力重分布特征而表现为极值点失稳模态;全钢试件上设置30 mm厚的UHPC层后,可使其弹性轴压刚度和抗压稳定承载力分别提高102.1%和119.7%;相比于具有相同换算截面面积的厚钢面板全钢试件,钢-UHPC组合试件的抗压稳定承载力仍可提高22.2%;与U肋截面面积及绕强轴惯性矩相等的T肋具有更好的局部稳定性,但因其抗扭性能较低,使得T肋加劲的钢-UHPC组合试件发生了整体弯扭屈曲破坏,但承载能力与U肋加劲试件相近。综合考虑受压钢构件和钢-UHPC组合构件的不同受力特征,提出了钢-UHPC组合桥面板的抗压稳定承载力计算公式,并以试验结果验证了其适用性。

     

    Abstract: To identify the compressive stability of the steel–ultra-high performance concrete (UHPC) composite deck structures in the light-weight composite girder systems of cable-stayed bridges, based on the test parameters including steel flange thickness, UHPC layer thickness, and stiffener shapes, five steel and steel–UHPC composite deck specimens with a geometric scale ratio of 1∶2 were designed and fabricated, and their compressive stability was investigated experimentally. The results show that: Steel specimens exhibit branch point instability mode, and the composite specimens possess high post-buckling bearing capacity with extreme point instability mode due to the strengthening effect of UHPC layer and the internal stress/force redistribution characteristics between steel and UHPC layer on the section where the steel is subjected to local buckling. Setting a 30 mm UHPC layer on the steel specimens can increase their elastic axial stiffness and compressive stability bearing capacity by 102.1% and 119.7%, respectively. Compared with the steel specimens with the same transformed cross-sectional area, the compressive stability bearing capacity of the steel-UHPC composite specimens can still be increased by 22.2%. The T-rib, which has the same cross-sectional area and moment of inertia around the strong axis as the U-rib, has better local stability; however, due to its lower torsional performance, the steel-UHPC composite specimens reinforced with T-ribs suffer overall flexural-torsional buckling failure, but the bearing capacity is similar to those of the specimens reinforced with U-ribs. A calculation formula for the bearing capacity of steel–UHPC composite decks under compressive stability was proposed based the different mechanical behaviors of steel and steel–concrete composite compressive members, and the applicability of formula was verified by the experimental results.

     

/

返回文章
返回