斜拉桥主梁钢-UHPC组合桥面板抗压稳定性能试验研究

EXPERIMENTAL STUDY ON COMPRESSIVE STABILITY OF STEEL–UHPC COMPOSITE DECKS FOR MAIN GIRDERS OF CABLE-STAYED BRIDGES

  • 摘要: 为明确大跨斜拉桥轻型组合主梁中钢-超高性能混凝土(ultra-high performance concrete,UHPC)组合桥面板的抗压稳定性能,以钢面板厚度、UHPC层厚度以及加劲肋形状等为试验参数,设计制作了5个1∶2几何缩尺比全钢和钢-UHPC组合桥面板试件并分别对其轴压稳定性能进行了试验研究。结果表明:全钢试件均呈现分支点失稳模态,组合试件由于UHPC层的加强作用及钢板件局部屈曲后截面上钢与UHPC层间存在的应力重分布特征而表现为极值点失稳模态;全钢试件上设置30 mm厚的UHPC层后,可使其弹性轴压刚度和抗压稳定承载力分别提高102.1%和119.7%;相比于具有相同换算截面面积的厚钢面板全钢试件,钢-UHPC组合试件的抗压稳定承载力仍可提高22.2%;与U肋截面面积及绕强轴惯性矩相等的T肋具有更好的局部稳定性,但因其抗扭性能较低,使得T肋加劲的钢-UHPC组合试件发生了整体弯扭屈曲破坏,但承载能力与U肋加劲试件相近。综合考虑受压钢构件和钢-UHPC组合构件的不同受力特征,提出了钢-UHPC组合桥面板的抗压稳定承载力计算公式,并以试验结果验证了其适用性。

     

    Abstract: To identify the compressive stability of the steel-ultra-high performance concrete (UHPC) composite deck structures in the light-weight composite girder systems of cable-stayed bridges, based on the test parameters including steel flange thickness, UHPC layer thickness, and stiffener shapes, five steel and steel-UHPC composite deck specimens with a geometric scale ratio of 1∶2 were designed and fabricated, and their compressive stability was investigated experimentally. The results show that: Steel specimens exhibit branch point instability mode, and the composite specimens possess high post-buckling bearing capacity with extreme point instability mode due to the strengthening effect of UHPC layer and the internal stress/force redistribution characteristics between steel and UHPC layer on the section where the steel is subjected to local buckling. Setting a 30 mm UHPC layer on the steel specimens can increase their elastic axial stiffness and compressive stability bearing capacity by 102.1% and 119.7%, respectively. Compared with the steel specimens with the same transformed cross-sectional area, the compressive stability bearing capacity of the steel-UHPC composite specimens can still be increased by 22.2%. The T-rib, which has the same cross-sectional area and moment of inertia around the strong axis as the U-rib, has better local stability; however, due to its lower torsional performance, the steel-UHPC composite specimens reinforced with T-ribs suffer overall flexural-torsional buckling failure, but the bearing capacity is similar to those of the specimens reinforced with U-ribs. A calculation formula for the bearing capacity of steel-UHPC composite decks under compressive stability was proposed based the different mechanical behaviors of steel and steel-concrete composite compressive members, and the applicability of formula was verified by the experimental results.

     

/

返回文章
返回