邓明科, 马向琨, 张伟, 李宁. 高延性混凝土加固蒸压加气混凝土砌体墙抗震性能试验研究[J]. 工程力学, 2021, 38(7): 9-18. DOI: 10.6052/j.issn.1000-4750.2020.06.0336
引用本文: 邓明科, 马向琨, 张伟, 李宁. 高延性混凝土加固蒸压加气混凝土砌体墙抗震性能试验研究[J]. 工程力学, 2021, 38(7): 9-18. DOI: 10.6052/j.issn.1000-4750.2020.06.0336
DENG Ming-ke, MA Xiang-kun, ZHANG Wei, LI Ning. EXPERIMENTAL STUDIES ON ASEISMIC BEHAVIOR OF AUTOCLAVED AERATED CONCRETE MASONRY WALLS STRENGTHENED WITH HDC[J]. Engineering Mechanics, 2021, 38(7): 9-18. DOI: 10.6052/j.issn.1000-4750.2020.06.0336
Citation: DENG Ming-ke, MA Xiang-kun, ZHANG Wei, LI Ning. EXPERIMENTAL STUDIES ON ASEISMIC BEHAVIOR OF AUTOCLAVED AERATED CONCRETE MASONRY WALLS STRENGTHENED WITH HDC[J]. Engineering Mechanics, 2021, 38(7): 9-18. DOI: 10.6052/j.issn.1000-4750.2020.06.0336

高延性混凝土加固蒸压加气混凝土砌体墙抗震性能试验研究

EXPERIMENTAL STUDIES ON ASEISMIC BEHAVIOR OF AUTOCLAVED AERATED CONCRETE MASONRY WALLS STRENGTHENED WITH HDC

  • 摘要: 蒸压加气混凝土(AAC)砌块砌体墙自重轻,但其抗震性能较差,为提高该类墙体的抗震性能,提出采用高延性混凝土(HDC)面层和条带对其进行加固。设计制作了4个无筋砌体墙和2个构造柱约束墙体试件,其中2个试件采用HDC面层加固,2个试件采用HDC条带加固,通过拟静力试验,研究AAC砌体墙的破坏形态、滞回性能、承载力及变形能力等性能。试验结果表明:HDC面层可改变AAC墙体的破坏模式;对于无筋砌体墙,加固后试件的承载力、变形及耗能能力均得到了不同程度的提高,墙体裂缝数量明显减少,刚度退化较为平缓;对于构造柱约束墙体,单面HDC面层使加固试件的侧向刚度、水平承载力及耗能能力均大幅提高,且加固试件具有较高的残余承载力,墙体的开裂和损伤程度较小。基于试件的破坏形态,提出加固墙体的水平承载力计算方法,其计算结果与试验结果吻合较好,可为HDC加固AAC砌块墙体的承载力计算提供参考。

     

    Abstract: Autoclaved aerated concrete (AAC) block masonry wall has the characteristic of light weight but poor aseismic performance. High ductile concrete (HDC) layer and strip were used for improving the aseismic performance of AAC masonry load-bearing walls. Four unreinforced masonry walls and two confined walls were designed. Among these specimens, two specimens were strengthened with single-sided HDC layer and two specimens were strengthened with HDC strips. The effects on the failure patterns, the hysteretic performance, the lateral strength and the deformability of each specimen were studied by a quasi-static test. Test results show that the single-sided HDC layer can change the failure modes of AAC masonry walls. For unreinforced masonry walls, HDC can significantly reduce the cracks and improve the stiffness degradation, the lateral strength, the deformability and the energy consumption capacity of AAC masonry walls. For confined masonry walls, the lateral stiffness, the horizontal bearing capacity and the energy consumption capacity of the confined wall strengthened with single-sided HDC layers were greatly improved, with high residual bearing capacity and slight damage. Based on the failure mode of specimens, a method for calculating the horizontal bearing capacity of strengthened walls is proposed, and the calculated results are in a good agreement with the experimental results, which can provide a reference for the calculation of bearing capacity of AAC block walls strengthened by HDC.

     

/

返回文章
返回