王树和, 张举兵. 基于地震损失风险钢筋混凝土框架结构弯矩增大系数评估[J]. 工程力学, 2018, 35(3): 132-140. DOI: 10.6052/j.issn.1000-4750.2016.11.0865
引用本文: 王树和, 张举兵. 基于地震损失风险钢筋混凝土框架结构弯矩增大系数评估[J]. 工程力学, 2018, 35(3): 132-140. DOI: 10.6052/j.issn.1000-4750.2016.11.0865
WANG Shu-he, ZHANG Ju-bing. EVALUATION OF MOMENT MAGNIFYING COEFFICIENTS OF RC STRUCTURES BASED ON THE SEISMIC RISK ASSESSMENT METHOD[J]. Engineering Mechanics, 2018, 35(3): 132-140. DOI: 10.6052/j.issn.1000-4750.2016.11.0865
Citation: WANG Shu-he, ZHANG Ju-bing. EVALUATION OF MOMENT MAGNIFYING COEFFICIENTS OF RC STRUCTURES BASED ON THE SEISMIC RISK ASSESSMENT METHOD[J]. Engineering Mechanics, 2018, 35(3): 132-140. DOI: 10.6052/j.issn.1000-4750.2016.11.0865

基于地震损失风险钢筋混凝土框架结构弯矩增大系数评估

EVALUATION OF MOMENT MAGNIFYING COEFFICIENTS OF RC STRUCTURES BASED ON THE SEISMIC RISK ASSESSMENT METHOD

  • 摘要: 损失是表征结构性能的综合指标。为了从损失风险的角度评估现行抗震规范钢筋混凝土框架弯矩增大系数的取值,基于地震风险评估框架FEMA P-58,给出了基于结构整体易损性分析的地震损失计算方法。设计了4个弯矩增大系数分别为1.1、1.3、1.5、1.7的钢筋混凝土框架结构,采用增量动力时程分析方法,得出了结构的易损性曲线和易损性矩阵,按照地震烈度概率模型,给出了所在场地各种烈度地震发生的概率,计算了每个结构在50年和1年内的经济损失和人员伤亡损失。结果表明,地震损失风险随强柱弱梁系数增大而减小,50年总经济损失比介于0.08~0.12,人员损伤率介于4.85×10-4~1.12×10-3。按照目前规范取值设计的结构地震损失风险处于可接受范围内。

     

    Abstract: Loss is a comprehensive index of structural seismic performance. In order to evaluate the rationality of moment magnifying coefficients of concrete frame structures in the current national seismic code, a method of seismic loss calculation was proposed. The method was based on structural fragility analysis and the loss calculation frame FEMA P-58, and was from the viewpoint of seismic loss risk. Four reinforced concrete frame structures with moment magnifying coefficients of 1.1, 1.3, 1.5, 1.7 were designed. The fragility curves and fragility matrixes were obtained by using the incremental dynamic analysis. According to the seismic intensity probability model, the probability distribution of various seismic intensity of the site was given. The 50-year and annual monetary and human losses of every structure were calculated. The results indicate that the seismic loss risk will decrease with the increase in moment magnifying coefficient. The 50-year total monetary loss ratio ranges between 0.08 and 0.12. The human loss ratio ranges between 4.85×10-4 and 1.12×10-3. The seismic loss risk is acceptable if the structure is designed to the current national design code.

     

/

返回文章
返回