白亮, 谢鹏飞, 周天华, 张轶. 钢管约束高强混凝土剪力墙压弯承载力及截面变形能力设计方法研究[J]. 工程力学, 2017, 34(11): 175-183. DOI: 10.6052/j.issn.1000-4750.2016.07.0551
引用本文: 白亮, 谢鹏飞, 周天华, 张轶. 钢管约束高强混凝土剪力墙压弯承载力及截面变形能力设计方法研究[J]. 工程力学, 2017, 34(11): 175-183. DOI: 10.6052/j.issn.1000-4750.2016.07.0551
BAI Liang, XIE Peng-fei, ZHOU Tian-hua, ZHANG Yi. STUDY ON DESIGN METHOD OF AXIAL FORCE-MOMENT CAPACITY AND SECTIONAL DEFORMATION CAPACITY OF STEEL TUBE CINFINED HIGH-STRENGTH CONCRETE SHEAR WALLS[J]. Engineering Mechanics, 2017, 34(11): 175-183. DOI: 10.6052/j.issn.1000-4750.2016.07.0551
Citation: BAI Liang, XIE Peng-fei, ZHOU Tian-hua, ZHANG Yi. STUDY ON DESIGN METHOD OF AXIAL FORCE-MOMENT CAPACITY AND SECTIONAL DEFORMATION CAPACITY OF STEEL TUBE CINFINED HIGH-STRENGTH CONCRETE SHEAR WALLS[J]. Engineering Mechanics, 2017, 34(11): 175-183. DOI: 10.6052/j.issn.1000-4750.2016.07.0551

钢管约束高强混凝土剪力墙压弯承载力及截面变形能力设计方法研究

STUDY ON DESIGN METHOD OF AXIAL FORCE-MOMENT CAPACITY AND SECTIONAL DEFORMATION CAPACITY OF STEEL TUBE CINFINED HIGH-STRENGTH CONCRETE SHEAR WALLS

  • 摘要: 通过剪跨比为2.1的钢管约束高强混凝土剪力墙试件低周反复加载试验,研究其在压弯荷载作用下的破坏形态、机理及耗能能力。试验表明,通过在高强混凝土剪力墙约束边缘构件内设置钢管,可提高其延性。在试验研究基础上,对钢管约束高强混凝土剪力墙压弯承载力及变形能力进行分析。考虑内置钢管约束影响,建立钢管约束高强混凝土剪力墙压弯承载力计算公式。根据截面平衡条件和变形条件,计算钢管约束高强混凝土剪力墙位移延性系数,得到钢管套箍率、轴压比及墙体高宽比与位移延性系数之间关系。研究表明,增加钢管套箍率及控制墙体轴压比,可以提高钢管约束高强混凝土剪力墙延性;提出满足不同变形能力要求,对应各种轴压比情况下,钢管约束高强混凝土剪力墙钢管套箍率建议设计值。

     

    Abstract: Cyclic loading tests of steel tube confined high-strength concrete shear walls with shear span ratios of 2.1 were conducted, and the failure pattern, mechanism and deformability under axial force-moment load were studied. The test shows that by providing confinement to the wall panel with steel tube, the ductility of specimens are improved. Based on experimental results, axial force-moment capacity and deformation capacity of steel tube confined high-strength concrete shear walls were analyzed. By considering the confinement of steel tube, axial force-moment capacity formula was established. Based on the equilibrium and deformation condition, the displacement ductility ratio of steel tube confined high-strength concrete shear walls was calculated. The mutual relationships among steel stirrup ratio, axial compression ratio, aspect ratio and displacement ductility ratio were obtained. The result shows that enhancing steel stirrup ratio and restraining axial compression ratio can improve ductility performance. Furthermore, the steel stirrup ratios with various deformation capacity and axial compression ratios are recommended.

     

/

返回文章
返回